Technical data.
Fire rated cable conforms to IEC/EN 60332-3-24; EN 60332-3-25 Flame retardant as per IEC/EN 60332.1-2.
Temperatures.
Operating: 0°C to 80°C.
Conductor max: 180°C
Short Circuit: 350°C
Voltage Rating.
U0/U 300/500 V
Min. Bending Radius.
10 x 0D
Halogen Free.
<0.5 mg/g (EN 50267-2-1; IEC 60754.1; IEC 60754.2)
Low Smoke Emission.
Transmittance > 60% (IEC 61034-8).
Application.
Fire rated cables are designed to ensure circuit continuity in the event of a fire. Primarily intended for use in fire detection and fire alarm systems, emergency lighting circuits or if cables need to operate when fire resistance is required. Suitable for indoor installations. Cable shielded with Aluminium/Polyester and unshielded.
Additional.
Cable Print: FIRE-TEC 2 x 1.00 100/100V PH30(/120), CEI 20-105 UNI 9795 CEI UNEL 36762 C-4 (Production batch) CE (Meter marking).
Marking Color: Blue.
Construction.
Annealed copper conductors as per EN 60228 class 5.
Core insulation ceramifiable silicone rubber.
Twisted pairs with polyester foil tape.
Annealed stranded tin copper drain wire.
Shielded with aluminium/PET foil.Outer sheath thermoplastic halogen free compound (T17) as per EN 50363-3; EN 50267-2-1.
Outer sheath color: Red.
Fire Resistance.
Ph30: 120 minutes at 830°C in accordance with EN50200 30 minutes at 950°C in accordance with BS 6387 cat. CWZ Ph120: 120 minutes at 950°C per BS 6387 cat. CWZ.
Variations.
Outer sheath Red or White. Additional colors on request. Alternatively, available in mineral fibre (Mica) Construction per EN502200.
X = PH30 / PH120.